Surge Suppression Technologies for AC Mains Compared
(MOVs, SADs, Gas Tubes, Filters and Transformers)
Application Note
January 1998
AN9310.1
Synopsis
[ /Title
(AN93
10)
/Sub-
ject
(Surge
Sup-
pres-
sion
Tech-
nolo-
gies
for AC
Mains
Com-
pared
(MOV
s,
SADs,
Gas
Tubes,
Filters
and
Trans-
form-
ers))
/Autho
r ()
/Key-
words
(Surge
Sup-
pres-
sion
Tech-
nolo-
gies
for AC
Protection on the low voltage AC mains system from
transient overvoltages is now a fundamental power quality
concern. The use of correctly selected and installed surge
protectors have a long and proven history of successful field
performance. The expected transient environment is
addressed, along with various types of surge suppression
components are compared to MOVs.
outages or combinations of the above and are generically
known as transients. A common result of encountering these
overvoltages is the early failure of semiconductor
components and other sensitive electrical components. An
equally serious effect is the loss of control in solid-state logic
systems that may think surges are legitimate signals and
thus endeavor to react to them.
Numerous studies have been performed which indicate that
the causes of the surges in an electrical system can be
attributed to one of the following causes:
•
•
•
•
•
•
Lightning
Opening or closing of switch contacts under load
Propagation of surges through transformers
Severe load changes in adjacent systems
Power line fluctuations and pulses
Short circuits or blown fuses
Introduction
The increasing use of semiconductors and other solid state
components in modern electrical systems has resulted in a
growing awareness about system reliability. This is a
consequence of the fact that solid state devices are very
susceptible to stray electrical transients which may be
present in the low voltage AC distribution system. The initial
use of semiconductors resulted in a large number of
unexplained failures. Investigation into these failures
revealed that they were caused by a number of diverse
overvoltage conditions which were present in the distribution
system. Transient voltages result from the sudden release of
previously stored energy from overstress conditions such as
lightning, inductive load switching, electromagnetic pulses or
electrostatic discharges. The severity of, and hence the
damage caused, by the transient depends on their frequency
of occurrence, their peak values and their waveshapes.
Electrical overvoltages on AC mains can cause either
permanent deterioration, or temporary malfunctions in
electronic components and systems. Protection from
transients can be obtained by using specially designed
components which will, either limit the magnitude of the
transient using a large series impedance or by diverting the
transient using a low value shunt impedance.
A prudent designer will consider the need for transient
protection in the early stages of the design. Too many times
it has been necessary to retrofit existing equipment with
transient suppressors. This is expensive in terms of field
failures, customer downtime and potential loss of business.
In some systems retrofitting becomes cumbersome, as the
space required was not planned for in the initial design. The
device selected as the system protector must have the
capability to dissipate the impulse energy of the transient at
a sufficiently low voltage so that the capabilities of the
system being protected are not affected.
The power system is made up of a large network of cross
connected transmission lines. This power system is often
interfered with by transients originating from one of the
aforementioned sources.
Transients caused by lightning can inject very high currents into
the system. These lightning strikes, usually to the primary
transmission lines, may result in coupling to the secondary line
through mutual inductive or capacitive coupling. Even a
lightning hit that misses the line can induce substantial voltage
onto the primary conductors, triggering lightning arresters and
creating transients. Man-made switching transients can be of a
lesser, but more frequent threat. Switching of the power grid
can cause transients which may damage down line equipment.
The use of thyristors in switching circuits or power control can
also create such transients.
Studies and laboratory investigation of residential and
industrial low voltage AC power systems have shown that
the amplitude of the transient is proportional to the rate of its
occurrence, i.e., lower magnitude transients occur most
often. Governing standards bodies, in particular lEEE and
ANSl, have established a document which gives practical
guidelines of the transient environment one may expect to
encounter in a low voltage AC power system. This document
is called the ANSl/lEEE standard C62.41 and was developed
in 1980. Since its inception, more accurate information has
become available on the transient environment and this has
led to the generation of an updated standard, which should
be available later this year.
Problem Definition
(The Transient Environment)
[1, 2, 3, 4]
Primarily the problem is that of the enigmatic presence of
overvoltage surges, above the normal system voltage.
Overvoltages are sometimes explainable or sometimes they
just mysteriously appear in the electrical system; they take
the form of disturbances, notches, swells, sags, brownouts,
10-41
Rate of Occurrence
The rate of occurrence of surges varies quite a lot and is
dependent upon the particular power system. Rate is related
to the level of surges and low magnitude surges are more
common than high level surges. Data from many sources
have shown that surges of 1kV or less are relatively
common, while surges of 3kV are more rare. The data
1-800-4-HARRIS or 407-727-9207
|
Copyright
©
Harris Corporation 1998
Application Note 9310
generated from the studies was used to generate the curve
shown in Figure 1. This curve shows with certainty only a
relative frequency of occurrence, while the absolute number
of occurrences can be described in terms of “low exposure”,
“medium exposure” and “high exposure”.
NUMBER OF SURGES PER YEAR EXCEEDING
10
3
HIGH
EXPOSURE
SURGE CREST OF ABSCISSA
10
2
MEDIUM
EXPOSURE
recommended that the device selected have, as a minimum,
the capability to handle the conditions called out in location
Category A of Table 1. The optimum device would preferably
have a minimum capability of surviving the transient
occurrences called out in location Category B.
TABLE 1. SURGE VOLTAGES AND CURRENTS DEEMED TO
REPRESENT THE INDOOR ENVIRONMENT
IMPULSE
LOCATION
CATEGORY
A
B
Long Branch Circuits
and Outlets
Major Feeders and
Short Branch Circuits
WAVEFORM
0.5µs
100kHz
1.2/50µs
8/20µs
0.5µs
100kHz
MEDIUM
EXPOSURE
6kV
200A
6kV
3kA
6kV
500A
10
1
1
(SEE NOTE) SPARKOVER
OF CLEARANCES
10
-1
LOW
EXPOSURE
10
-2
0.3
0.5
1
2
5
SURGE CREST (kV)
10
20
NOTE: In some locations, sparkover of clearances may limit the
overvoltages.
FIGURE 1. RATE OF SURGE OCCURRENCES vs VOLTAGE
LEVEL AT UNPROTECTED LOCATIONS
An area described as a “low exposure” area would have very
little lightning activity and few switching loads on the AC power
system. A “medium exposure” area is known for high lightning
activity, with frequent and severe switching transients. When
designing equipment for the global environment it is expedient
that it be, at least, designed for use in an area with “medium
exposure” transient occurrences. “High exposure” areas are
rare but real systems supplied by long overhead transmission
lines and subject to reflections at line ends, where the
characteristics of the installation produce high sparkover
levels of the clearances.
All indoor low-voltage AC power systems have an inherent
protection system built into the wiring of the building. Wiring
systems used in 120V - 240V systems have a natural
sparkover level of 6000V. This 6kV level has therefore been
selected as the worst case cutoff for the occurrence of
transients in the indoor power system. The transient
generated by sparkover creates a high energy, low impedance
pulse. The further away from the source of the transient the
protected equipment is located, the more the energy is
absorbed in the wiring impedance and the more the
equipment is protected. This, therefore, allows different size
suppressors to be used at different locations in the system.
The investigation into the indoor low voltage system revealed
that location Category A encounters transients with
oscillatory waveshapes with frequency ranges from 5kHz to
more than 500kHz; the 100kHz being deemed most
common (Figure 2). Surges recorded at the service
entrance, location Category B, are both oscillatory and
unidirectional in nature. The typical “lightning surge” has
been established as 1.2/50µs voltage wave and 8/20µs
current wave (Figure 3).
V
PEAK
0.9 V
PEAK
T = 10µs (f = 100kHz)
0.1 V
PEAK
0.5µs
60% OF V
PEAK
FIGURE 2. 0.5µs - 100kHz RING WAVE (OPEN CIRCUIT VOLTAGE)
V
0.9V
PEAK
V
PEAK
0.3V
PEAK
0.5V
PEAK
Representative Transients
Table 1 reflects the surge voltages and currents deemed to
represent the indoor transient environment in a low-voltage
AC power system. When deciding on the type of device to
use as a transient voltage surge suppressor, it is
t
1
50µs
t
1
x 1.67 = 1.2µs
FIGURE 3A. OPEN-CIRCUIT WAVEFORM
10-42
Application Note 9310
I
0.9 I
PEAK
I
PEAK
Filters
The installation of a filter in series with the equipment seems an
obvious solution to overvoltage conditions. The impedance of a
low pass filter, e.g., a capacitor, forms a voltage divider with the
source impedance. As the frequency components of a transient
are several orders of magnitude above the power frequency of
the AC circuit, the inclusion of the filter will result in attenuation
of the transient at high frequencies. Unfortunately, this simple
approach may have some undesirable side affects; a)
unwanted resonances with inductive components located
elsewhere in the system leading to high voltage peaks, b) high
inrush currents during switching and c) excessive reactive load
on the power system voltage. These undesirable effects can be
reduced by adding a series resistor, hence the popular use of
RC snubber networks. However, the price of the added
resistance is less effective clamping.
There is a fundamental limitation to the use of a filter for
transient suppression. Filter components have a response
which is a linear function of current. This is a big
disadvantage in a situation where the source of the transient
is unknown and it is necessary to assume a source
impedance or an open-circuit voltage. If the assumption of
the characteristics of the impinging transient are incorrect
the consequences for a linear suppressor is dramatic. A
slight change in the source impedance can result in a
disproportionately increase in clamping voltage [6].
0.5 I
PEAK
0.1 I
PEAK
t
2
20µs
t
2
x 1.25 = 8µs
FIGURE 3B. DISCHARGE CURRENT WAVEFORM
FIGURE 3. UNIDIRECTIONAL WAVESHAPES (OUTDOOR
LOCATIONS)
Transient Protection
Once it has been decided to include transient suppression in
the design of equipment, the next stage in the process is to
decide on what protection technology to use and on how to use
it. The transient suppressor selected must be able to suppress
surges to levels which are below the failure threshold of the
equipment being protected, and the suppressor must survive a
definite number of worst case transients. When comparing the
various devices available considerations must be given to
characteristics such as protection levels required, component
survivability, cost, and size.
There are a number of different technologies available for
use as a transient suppressor in the low voltage AC mains
system. Generally speaking, these can be grouped into two
major categories of suppressors: a) those that attenuate
transients, thus preventing their propagation into the
sensitive circuit; and b) those that divert transients away
from sensitive loads and so limit the residual voltage.
Attenuating a transient - that is, keeping it from propagating
away from its source or keeping it from impinging on a sensitive
load - is accomplished with by placing either filters or isolating
transformers in series within a circuit. The
isolator
attenuates
the transient (high frequency) and allows the signal or power
flow (low frequency) to continue undisturbed.
Diverting the transient can be accomplished with a crowbar
type device or with a voltage clamping device.
Crowbar
device types involve a switching action, either the breakdown
of a gas between electrodes or the turn on of a thyristor.
After switching on, they offer a very low impedance path
which diverts the transient away form the parallel-connected
load.
Clamping
devices have a varying impedance which
depends, either, on the current flowing through the device or
on the voltage across the terminals. These devices exhibit a
nonlinear impedance characteristic. The variation of the
impedance is monotonic; that is, it does not contain
discontinuities in contrast to the crowbar device, which
exhibits a turn on action.
10-43
Isolation Transformers
Isolation transformers generally consist of a primary and
secondary windings with an electrostatic shield between the
windings. The isolation transformer is placed between the
source and the equipment requiring protection. As its name
suggests, there is no conduction path between the primary and
secondary windings. A widely held belief is that “isolation
transformers attenuate voltage spikes” and “that transients do
not pass through the windings of the transformer”. When
properly applied, the isolation transformers is useful to break
ground loops, i.e., block common-mode voltages.
Unfortunately, a simple isolation transformer provides no
differential-mode attenuation [7]. Thus, a differential-mode
transient will be transmitted through the windings of the
device. Also, an isolation transformer will not provide any
voltage regulation.
Spark Gaps and Gas Tubes
Spark gap suppression is a crowbar suppression technology.
During an overvoltage condition, a crowbar device changes
from being an insulator to an almost ideal conductor.
Crowbars suppress transients by brute force, (they have the
effect of dropping a metal crowbar across the system). The
main type of crowbar device is the gas tube surge arrester.
The original offering in the spark gap surge suppression family
was a carbon blocks. The carbon block suppressor used the
principle of a voltage arcing across an air gap. The air gap
breaks down at approximately 150V per thousands of an inch.
The minimum size gap was used to provide the lowest level of
protection without disturbing regular system operation. When a
Application Note 9310
transient overvoltage occurred in the system, the air gap in the
carbon block would ionize and break down. The breakdown of
the gap forms a very low impedance path to ground thus
diverting the surge away from the equipment. As soon as the
overvoltage condition was removed, the air gap is restored and
system operation is continued.
The disadvantage of carbon block spark gap technology was
that short duration pulses “pitted” the surface of the carbon
blocks, thus removing small pieces of the face material. This
material builds up after a number of surges, eventually
causing a permanently shortened gap resulting in the need
for protector replacement. This had a very adverse effect on
the maintenance and replacement costs of the protection
circuit. Another disadvantage of this technology was the
difficulty in exactly controlling the breakdown characteristics
over a wide variety of operating conditions.
In an effort to overcome the disadvantages of the carbon
block, a sealed spark gap was developed which uses an
inert gas in a sealed ceramic envelope. This technology is
known as a gas tube surge arrester. In a non conducting
mode the impedance of the gas is in the gigiohms region.
The gas is set to ionize at a predetermined voltage and
offers an extremely low impedance path to ground. Once the
overvoltage condition is removed the gas deionizes and the
circuit restores itself to its normal operating condition.
The gas tube arrester is an inherently bidirectional device and
is comprised of either two or three electrodes lying opposite
each other in the sealed chamber. When the voltage across the
arrester terminals exceeds a certain limit, known as the firing or
breakdown voltage, it triggers an electric arc. This arc limits the
voltages applied to the connected equipment. Gas tubes have
typical DC firing voltages between 150V and 1000V. They have
the smallest shunt resistance of all nonlinear transient
suppressors, typically in the milliohm range. Their capacitance
is low, between 1pF and 5pF, and they are commonly found in
high frequency transmission applications, such as telephone
systems. Another advantage of this technology is its ability to
handle large currents (up to 20kA).
In applications where there is a normal operating voltage, as
in the AC mains, there is a possibility that the gas tube will not
reset itself once it has fired and suppressed the transient. This
condition is known as follow on current and is defined by ANSl
“as the current that passes through a device from the
connected power source following the passage of discharge
current”. Follow on current will maintain conduction of the
ionized gas after the transient has disappeared and the
concern is that the follow on current may not clear itself at a
natural current zero. A gas tube specifically designed for AC
line operation should be used in this type of application.
the tightest clamping voltage of available devices. When a
voltage greater than the device breakdown is applied, the diode
will conduct in the reverse direction.
A peak pulse power rating is usually given on diode data
sheets. Common values are 600W and 1500W. This peak
pulse power is the product of the maximum peak pulse current,
I
PP
, and the maximum clamping voltage, V
C
, at a current of
I
PP
during a 10/1000µs transient duration. Use of peak power
ratings may be confusing when transients of other than
10/1000µs are to be considered. A maximum energy rating for
non-repetitive, short duration transients, similar to that supplied
with MOVs, may be of more benefit to design engineers.
The V-l characteristics are the best features of the avalanche
diode. Low voltage devices look extremely good. The
avalanche diodes has an excellent clamping voltage
capability, but only over a small range of current (1 decade).
The biggest disadvantage to using the avalanche diode as a
transient suppressor on an AC mains line is its low peak
current handling capability. Due to their being, at most, only
two P-N junctions in a device their is very little material
available for the dissipation of the peak power generated
during high energy pulses.
Metal Oxide Varistor (MOV)
[6]
A metal oxide varistor (MOV) is a nonlinear device which has
the property of maintaining a relatively small voltage change
across its terminals while a disproportionately large surge
current flows through it. This nonlinear action allows the
MOV to divert the current of a surge when connected in
parallel across a line and hold the voltage to a value that
protects the equipment connected to that line. Since the
voltage across the MOV is held at some level higher than the
normal line voltage while surge current flows, there is energy
deposited in the varistor during its surge diversion function.
The basic conduction mechanism of a MOV results from
semiconductor junctions (P-N junctions) at the boundaries of
the zinc oxide grains. A MOV is a multi junction device with
millions of grains acting as a series-parallel combination
between the electrical terminals. The voltage drop across a
single grain in nearly constant and is independent of grain size.
The material of a metal oxide varistor is primarily zinc oxide
with small additions of bismuth, cobalt, manganese and
other metal oxides. The structure of the body consists of a
matrix of conductive zinc oxide grains separated by grain
boundaries, which provide the P-N junction semiconductor
characteristics. When the MOV is exposed to surges, the
zinc oxide exhibits a “bulk action” characteristic permitting it
to conduct large amounts of current without damage. The
bulk action is easily explained by imagining this material to
be made up of an array of semiconducting P-N junctions
arranged electrically in series and parallel so that the surge
is shared among all of the grains. Because of the finite
resistance of the grains, they act as current limiting resistors
and, consequently current flow is distributed throughout the
bulk of the material in a manner which reduces the current
concentration at each junction.
Silicon Avalanche Diodes
Although rarely used on AC mains application, due to their very
low transient surge capability, silicon avalanche diodes are an
excellent surge suppressor in low voltage DC applications.
Avalanche diodes are designed with a wider junction than a
standard zener diode. This wide junction gives them a greater
ability than a zener to dissipate energy. Avalanche diodes offer
10-44
Application Note 9310
The MOV has many advantages which make it ideal for use
as a suppressor on the low voltage AC power line. The bulk
nature of its construction gives it the required energy
handling capability to handle the secondary level transients
resulting from indirect lightning hits.
MOVs are both cost and size effective, are widely available
and do not have a significant amount of overshoot. The
flexibility available in the manufacturing of these devices
means that different size varistors are available for transient
suppression in all categories of the ANSl/lEEE C62.41
standard. They have no follow on current and their response
time is more than sufficient for the types of transients
encountered in the AC mains environment.
A common misconception is that the device is irreversibly
damaged every time it has to suppress a transient. Under
high energy transient conditions in excess of the device
ratings, the V-I characteristics of the varistor are seen to
change. This change is reflected in a decrease in the
nominal varistor voltage. After applying a second or third
pulse the nominal varistor voltage can be seen to return to
its original value (Figure 4). To be conservative, peak pulse
limits have been established which, in many cases, have
been exceeded many fold without causing harm to the
device. Field studies and laboratory tests have shown that
the degradation which may result, after a number of pulses
outside the ratings of the device, is safe for the equipment
being protected. This does not mean that the established
limits should be ignored but rather viewed in the perspective
of the definition of a failed device. A “failed” device is defined
by a
±10%
change in the nominal varistor voltage at the 1mA
point. This does not imply a non-protecting device, but rather
a device whose clamping voltage has been slightly altered.
45
TABLE 2. COMPARATIVE PERFORMANCE DATA [8]
PROTECTION
TECHNOLOGY
Metal Oxide
Varistor
DEVICE
PART
NUMBER
V130LA1
V130LA5
V130LA10A
Silicon Avalanche
Diode
Gas Tube Surge
Arrester
Filter Capacitor
1.5KE200C
CG2-230
C280A-
EA4K7
AVERAGE
PROTECTION
LEVEL (kV)
0.51
0.50
0.49
0.48
0.67
1.30
FAILS/
SAMPLE
SIZE
0/10
0/10
0/10
2/10
0/10
0/10
Device Selection
To select the correct varistor for a specific application,
determine the following information:
1. The maximum system RMS voltage.
2. How is the MOV to be connected?
3. The MOV with a voltage 10% - 25% above system
voltage.
4. The worst-case transient energy that will need to be
absorbed by the MOV. (Use the guidelines called out in
ANSI/IEEE C62.41 -1980).
5. The clamping voltage required for system protection (As
device size increases, for a given voltage family, the
clamping voltage gets better).
References
For Harris documents available on the web, see
http://www.semi.harris.com/
Harris AnswerFAX (407) 724-7800.
[1]
“ANSl/IEEE C62.41 -1980 Guide On Surge Voltages In
Low-Voltage AC Power Circuits”.
[2]
“AC Line Voltage Transients and Their Suppression”,
Corbett, M., Application Note AN9308, Harris
Suppression Products, AnswerFAX Doc. No. 99308.
VOLTS AT 1mA
40
35
[3]
“Understanding AC Line Transient Immunity”,
Dash, G.
and Straus, l.
30
0
1
2
3
4
5
6
7
NUMBER OF PULSES
8
9
10
[4]
“Suppression Of Voltage Transients Is An Art Trying To
Be A Science”,
GE # 660.33.
[5]
“Surge Protection of Electronics”,
Haskell, Jr., N.H., P.E.
[6]
“Transient Voltage Suppression Devices”,
Harris
Suppression Products DB450.
[7]
“The Propagation and Attenuation of Surge Voltages
and Currents in Low Voltage AC Circuits”,
Martzloff,
F.D., - 1984.
[8]
“Protective Level Comparison of Voltage Transient
Suppressors”,
Hopkins, D.C.
[9]
“Comparison of Transient Suppressors!”,
Korn, S.
FIGURE 4. REPETITIVE PULSE WITHSTAND CAPABILITIES
Device Comparisons
A range of standard varistors, avalanche diodes, gas tube
arresters and filter capacitors were evaluated under a 6kV,
0.5µs x 100kHz ring wave. This transient replicates that called
out in location Category A of the ANSl/lEEE C62.41 and is the
most benign condition expected in this location. All of the
selected devices are rated for use on a 120V
AC
line. The
results obtained from this evaluation are per Table 2.
10-45
Plik z chomika:
michalr1n
Inne pliki z tego folderu:
kicad-product-4.0.1-x86_64(1).exe
(238111 KB)
KiCad_stable-2013.07.07-BZR4022_Win_full_version(1).exe
(202387 KB)
kicad-product-4.0.1-i686(1).exe
(238403 KB)
kicad-product-4.0.1-i686.exe
(238403 KB)
kicad-product-4.0.1-x86_64.exe
(238111 KB)
Inne foldery tego chomika:
Pliki dostępne do 01.06.2025
Pliki dostępne do 19.01.2025
! Crystal Reports
! HTML CSS XHTML
█ STRZELANKI
Zgłoś jeśli
naruszono regulamin